75/100/155 Watts  
BCS Series  
xppower.com  
DC Standby System  
Battery Charging Output  
Optional 5 V, 3 A Supply  
Low Battery Disconnect  
AC OK and Battery Low Alarms  
Battery Overload & Reverse Polarity Protection  
3 Year Warranty  
Specification  
Input  
General  
Input Voltage  
Input Frequency  
Input Current  
• 90-264 VAC (120-370 VDC)  
• 47-63 Hz  
• 75 W: 1.5/1.0 A max 115/230 VAC  
100 W: 2.0/1.2 A max 115/230 VAC  
155 W: 2.5/1.5 A max 115/230 VAC  
Efficiency  
Isolation  
• See tables  
• 3000 VAC Input to Output  
1500 VAC Input to Ground  
500 VAC Output to Ground  
• 75 W: 40-76 kHz at full load typical  
100 W: 28-60 kHz at full load typical  
155 W: PFC 100 kHz, PWM 30-47 kHz at  
25-100% load typical  
• 75 W: 3.4 W/In ,100 W: 4.5 W/In ,  
155 W: 3.8 W/In  
• AC OK and BAT LOW signals,  
see applications note  
• 130 kHrs typical to MIL-HDBK-217F  
at 25 °C, GB  
Switching Frequency  
Inrush Current  
• 75/100 W 70 A max/230 VAC cold start 25 °C,  
155 W 80 A max/230 VAC cold start 25 °C  
Earth Leakage Current • <1 mA at 264 VAC, 60 Hz  
Power Factor  
Input Protection  
3
3
• Meets EN61000-3-2, class A  
• Internal 4.0 A (155 W: 5.0 A) 250 V fuse,  
fitted in line  
Power Density  
Signals  
3
Output  
Output Voltage  
MTBF  
• See tables  
Output Voltage Trim  
10% on output 1. Output 2 tracks by  
same percentage  
Environmental  
Initial Set Accuracy  
Minimum Load  
Start Up Delay  
1.0%  
Operating Temperature • -20 °C to +70 °C. Refer to derating curves  
Cooling  
• None  
• 75 & 100 W: Convection-cooled,  
155 W: Internal fan  
• 95% RH, non-condensing  
• 75/100 W: 800 ms O/P 1 & 3, 3.5 s O/P 2,  
155 W: 4 s O/P 1 & 3, 6.2 s O/P 2  
• 30 ms max  
• 8 ms min at 115 VAC  
• Output 1 & 2: 0.5%, Output 3: 1.5%  
(where fitted)  
• 5% max at turn on  
Operating Humidity  
Start Up Rise Time  
Hold Up Time  
Line Regulation  
Load Regulation  
Storage Temperature • -40 °C to +85 °C  
Operating Altitude  
Shock  
• 2000 m  
• 30 g pk, half sine, 6 axes  
• 2 g rms, 10 Hz to 500 Hz, 10 min/cycle for  
60 mins on each axis  
0.5% max  
Vibration  
Over/Undershoot  
Transient Response  
• 4% max. deviation, recovery to less than  
1% within 500 µs for step load change of  
25%  
• Output 1: 1% pk-pk, Output 2: 150 mV  
pk-pk, Output 3: 100 mV pk-pk (where  
fitted), 20 MHz bandwidth  
EMC & Safety  
Emissions  
• EN55022, Level B conducted and radiated  
• EN61000-3-2, class A  
• EN61000-3-3  
• EN61000-4-2, level 3 Perf Criteria A  
• EN61000-4-3, 3 V/m Perf Criteria A  
• EN61000-4-4, level 2 Perf Criteria A  
Ripple & Noise  
Harmonic Currents  
Voltage Flicker  
ESD Immunity  
Radiated Immunity  
EFT/Burst  
Overvoltage Protection • 115-150% on output 1 only, recycle mains  
to reset  
Overload Protection  
• Output 1: >110% of total rated power  
Output 2: 100-115% of max current  
Output 3: >3.3 A (where fitted)  
Surge  
• EN61000-4-5, installation class 3,  
Perf Criteria A  
• EN61000-4-6, 3 V Perf Criteria A  
• EN61000-4-11, 30% 10 ms, 60% 100 ms,  
100% 5000 ms, Perf Criteria A, B, B  
• EN60950-1, UL60950-1  
An overload on any output will affect the  
voltage regulation of all outputs  
• Internal battery relay opens at 10 V 4%  
for 13 V versions and 20 V 5% for 27 V  
versions  
Conducted Immunity  
Dips & Interruptions  
Batt. Low Voltage  
Protection  
Safety Approvals  
Short Circuit Protection • On all outputs, trip and restart, auto recovery  
Temp. Coefficient • 0.03%/°C