AC-DC Power Supplies
AEL15-80-L6 Series
Output
Characteristic
Min.
Typ.
Max.
Units
Notes & Conditions
Output Voltage
Minimum Load
5
48
See Models and Ratings table
No minimum load required
5
AEL15 at full load 110 VAC
Hold Up Time
10
16
ms
AEL20/40 at full load 110 VAC
AEL60/80 at full load 110 VAC
AEL20/40 at full load, 100 VAC
AEL15/60/80 at full load, 100 VAC
Maximum deviation, recovering to less than 1% within
500 µs for 50% step load
0.5
2.0
Start Up Delay
s
Transient Response
2
%
Measured with 20 MHz bandwidth and 10 µF electrolytic
capacitor in parallel with a 0.1 µF ceramic capacitor
Ripple and Noise
1
% pk-pk
Overvoltage Protection
Overload Protection
112
110
132
150
%
%
AEL40/60/80 models only
AEL20/40/60/80 models only
Short Circuit Protection
Temperature Coefficient
Trip and restart (hiccup)
0.04
%/°C
Environmental
Characteristic
Minimum
Typical
Maximum
Units
Notes & Conditions
Operating Temperature
Cooling
-20
+60
°C
Derate from 100% load at 40 °C to 50% load at +60 °C
Convection cooled
Operating Humidity
Storage Temperature
Operating Altitude
Shock
5
-40
95
+85
2000
%RH
°C
m
Non-condensing
10 g, 10 ms on 3 axes
General
Characteristic
Minimum
Typical
Maximum
Units
%
Notes & Conditions
Efficiency
See Models and Ratings table
3000
1500
500
VAC
VAC*
VDC*
kHz
Isolation: Input to Output
Input to Ground
*Not C8 version
Output to Ground
Switching Frequency
Mean Time Between Failure
Weight
63 KHz
>100
kHrs
MIL-HDBK-217F at 25 °C GB
0.36 (165)
0.37 (170)
0.64 (275)
0.79 (340)
1.5 (700)
AEL15
AEL20
AEL40
AEL60
AEL80
lb (g)
www.xppower.com
2