BCM
®
in a VIA Package
Bus Converter
BCM4414xG0F4440yzz
®
S
C
US
C
NRTL
US
Isolated Fixed-Ratio DC-DC Converter
Features & Benefits
•
Up to 40A continuous low voltage side current
•
Fixed transformation ratio (K) of 1/16
•
Up to
776W/in
3
power density
•
97.5% peak efficiency
•
Integrated filtering
•
Parallel operation for multi-kW arrays
•
OV, OC, UV, short circuit and thermal protection
•
4414 package
•
High MTBF
•
Thermally enhanced VIA package
•
PMBus™ management interface
•
Bidirectional operation (start up in forward direction only)
Product Ratings
V
HI
= 544V (400 – 700V)
V
LO
= 34V (25 – 43.8V)
(
no load
)
I
LO
= up to 40A
K = 1/16
Product Description
The BCM4414xG0F4440yzz in a VIA package is a high efficiency
Bus Converter, operating from a 400 to 700V
DC
high voltage bus
to deliver an isolated 25 to 43.8V
DC
unregulated, low voltage.
This unique ultra-low profile module incorporates DC-DC
conversion, integrated filtering and PMBus™ commands and
controls in a chassis or PCB mount form factor.
The BCM offers low noise, fast transient response and industry
leading efficiency and power density. A low voltage side
referenced PMBus compatible telemetry and control interface
provides access to the BCM’s configuration, fault monitoring, and
other telemetry functions.
Leveraging the thermal and density benefits of Vicor’s VIA
packaging technology, the BCM module offers flexible thermal
management options with very low top and bottom side
thermal impedances.
When combined with downstream Vicor DC-DC conversion
components and regulators, the BCM allows the Power Design
Engineer to employ a simple, low-profile design, which will
differentiate the end system without compromising on cost or
performance metrics.
Typical Applications
•
High Voltage DC Power Distribution
•
3 Phase AC-DC Converters
•
Information and Communication
Technology (ICT) Equipment
•
High End Computing Systems
•
Automated Test Equipment
•
Industrial Systems
•
High Density Energy Systems
•
Transportation
•
Green Buildings and Microgrids
Part Ordering Information
Product
Function
BCM
BCM =
Bus Converter
Module
[a]
Size:
4.35 x 1.40 x 0.37in
[110.55 x 35.54 x 9.40mm]
Max
High
Side
Voltage
G0
High
Max
Side
Low
Voltage
Side
Range
Voltage
Ratio
F
44
Max
Low
Product Grade
Side
(Case Temperature)
Current
40
y
C = –20 to 100°C
[a]
T = –40 to 100°C
[a]
Package
Length
44
Length in
Inches x 10
Package
Width
14
Width in
Inches x 10
Package
Type
x
B = Board VIA
V = Chassis VIA
Option Field
zz
02 = Chassis/PMBus
06 = Short Pin/PMBus
10 = Long Pin/PMBus
Internal Reference
High temperature current derating may apply; See Figure 1, specified thermal operating area.
BCM
®
in a VIA™ Package
Page 1 of 43
Rev 1.2
01/2018