欢迎访问ic37.com |
会员登录 免费注册
发布采购

TCL120112 参数 Datasheet PDF下载

TCL120112图片预览
型号: TCL120112
PDF下载: 下载PDF文件 查看货源
内容描述: [Industrial Power Supplies]
分类和应用:
文件页数/大小: 6 页 / 305 K
品牌: TRACOPOWER [ TRACO ELECTRONIC AG ]
 浏览型号TCL120112的Datasheet PDF文件第1页浏览型号TCL120112的Datasheet PDF文件第3页浏览型号TCL120112的Datasheet PDF文件第4页浏览型号TCL120112的Datasheet PDF文件第5页浏览型号TCL120112的Datasheet PDF文件第6页  
Industrial Power Supplies  
TCL Series  
24 to 240 Watt  
Input Specifications  
Input voltage range  
85–264 VAC/85–375 VDC  
TCL 240 model: 85–132/187–264 VAC autoselect (no DC input)  
Output derating  
– at operation between 85...93 VAC/85...130 VDC  
15% for TCL 060 & TCL 120  
20% for TCL 024-112 & TCL 024-124 & TCL 240  
30% for TCL 024-105  
Input frequency  
47–63 Hz  
Harmonic limits  
EN 61000-3-2, Class A  
Input current at full load (typ.) (115 VAC / 230 VAC)  
TCL 024 models: 0.35 A / 0.2 A  
TCL 060 models: 1.2 A / 0.6 A  
TCL 120 models: 2.0 A / 1.0 A  
TCL 240 model: 3.3 A / 1.7 A  
Recommended circuit breaker (characteristic C or slow blow fuse)  
5.0 A  
Output Specifications  
Output voltage adjustable range  
5.1 VDC model: 5.0 – 5.25 VDC  
(potentiometer on frontpanel)  
12 VDC models: 12 – 15 VDC (12 - 16 VDC for TCL 024-112)  
24 VDC models: 24 – 28 VDC  
48 VDC models: 48 – 56 VDC  
Output regulation (10 to 90% load variation)  
Ripple and noise (20MHz bandwidth)  
Electronic short circuit protection  
2.5 % (1 % for TCL 60-112)  
<50 mV pk-pk  
current limitation at 120 % typ.  
(constant current, automatic recovery  
TCL 24 models: foldback, automatic recovery)  
Parallel operation  
output current characteristic suitable for  
parallel operation of max. 5 units  
(not for TCL 240-124)  
Overvoltage protection, trigger point  
5.1 VDC model: <6.5 VDC  
12/24 VDC models: <40 VDC  
48 VDC models: <60 VDC  
Hold-up time (115 VAC / 230 VAC)  
min. 15 ms / min. 125 ms  
Power OK signal (TCL 60 & TCL 120 only)  
trigger  
point  
output signal  
(reference to – Vout)  
12 VDC models: >11V  
24 VDC models: >22V  
48 VDC models: >44V  
11.0 V 1.0 V / 60 mA max.  
22.0 V 2.0 V / 30 mA max.  
44.0 V 4.0 V / 15 mA max.  
General Specifications  
Temperature ranges  
– Operating  
–10°C to +70°C max.  
– Storage (non operating)  
–25°C to +85°C  
Temperature derating  
– at 187...264 VAC or 265...375 VDC operation  
– at 93...132 VAC or 130...187 VDC operation  
– at 85...130 VDC operation  
1.7 %/K above 50°C  
1.1 %/K above 40°C  
1.3 %/K above 30°C  
Humidity (non condensing)  
Temperature coefficient  
Switching frequency  
95 % rel. H max.  
0.02 %/K  
55 – 180 kHz depending on load  
(frequency modulation)  
Efficiency  
88 % typ.  
http://www.tracopower.com  
Page 2 of 6