Industrial Power Supplies  
TCL Series  
24–120 Watt  
General Specifications  
Safety standards  
IEC 60950, EN 60950 (output SELV),  
UL 60950, UL 508, EN 50178,  
EN 60204, EN 61558-2-8.  
- NEC class 2 (TCL 60 models only)  
Safety approvals (TCL 24 models pending)  
UL/cUL 60950 recognized, File E181381  
UL 508C listed, File E210002  
CB-Report per IEC 60950  
Electromagnetic compatibility (EMC), Emissions  
Electromagnetic compatibility (EMC), Immunity  
Safety class  
EN 61000-6-3  
EN 61000-6-2  
degree of protection class 1  
IP 20 (IEC 60529)  
Case protection  
Enclosure material  
plastic FR2010-110C (UL 94V-0 rated)  
Mounting  
35 mm DIN-rails as per EN 50022-35x15/7.5  
(snap-on with self-locking spring)  
Adapter for Wall-/Chassi Mounting (included)  
Options  
output characteristic optimized for battery  
charging available on request  
TCL–REM240 Redundancy Module  
This module enables redundant operation of any two TCL models by decoupling  
the 2 power supplies. It can also be used to separate sensitive loads from the main  
power source.  
Models  
Order code  
Inputs  
Vin  
Max power  
per input  
Output voltage  
Output current  
max.  
Connection  
TCL–REM240  
2 x 5...60 VDC  
144 W  
Vin – 0.9 VDC  
8 A  
detachable screw  
terminal block  
Specifications  
Operating temperature  
– 10°C...+70°C max. (14°F...+158°F)  
derating above 40°C (104°F): 1.5%/K  
Electromagnetic compatibility  
Dimensions  
in correspondence to connected units  
(no internal switching device)  
same as model TCL 24 (see page 4)  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
http://www.tracopower.com  
Page 3 of 5