TBLC Series, 6 – 90 W  
Input Specifications  
Input voltage  
– nominal ranges  
– effective ranges  
100 – 240 VAC; 50/60 Hz  
85 – 264 VAC; 47-63 Hz  
(below 100 VAC a derating of 2 %/V is required)  
Input voltage frequency  
47 – 63 Hz  
No load power consumption  
6–50 W models: < 0.3 W  
75–90 W models: < 0.5 W  
Harmonic limits  
Leakage current  
Inrush current  
EN 61000-3-2, class A  
0.25 mA max.  
6–50 W models: 15/30 A (115/230 VAC)  
75–90 W models: 25/50 A (115/230 VAC)  
Output Specifications  
Output voltage / current  
5 VDC models: 5.0 – 5.5 VDC*  
12 VDC models: 12.0 – 16.0 VDC*  
24 VDC models: 24.0 – 28.0 VDC*  
Regulation  
Hold-up time  
Start-up  
– Input variation  
– Load variation (10–90 %)  
0.3 % max.  
0.3 % max.  
60 ms min. (at 230 VAC)  
15 ms typ. (at 115 VAC)  
– Start up behavior  
– Start up time  
TBLC 75-112 and 90-112: 0-75 % constant current load  
other models: 0-100 % constant current load  
1 s max.  
Ripple and Noise (20 MHz bandwidth)  
Current limit (continuous)  
Short circuit current  
50 mVp-p max.  
105 – 130 % of Iout nom., constant current  
TBLC 75-112 and 90-112: 70 – 90 % of Iout nom. (typ.), foldback  
other models: 120 – 200 % of I out nom  
Output overvoltage protection  
150 % of Vout nom. (typ.)  
> 95 % of the set voltage  
DC OK signal  
– trigger threshold ON  
General Specifications  
Operating temperature  
–25°C to +70°C  
derating above +55ºC: 2.5 %/K  
Storage temperature  
Temperature coefficient  
Cooling  
–40°C to +85°C  
0.02 %/K  
convection cooling, no internal fan  
2
Pollution degree  
Humidity (non condensing)  
Altitude during operation  
5–95 % rel. H max.  
4800 m max.  
Isolation  
– I/O isolation  
3000 VAC (4242 VDC)  
safety class II  
Class of protection  
Degree of protection  
IP 20 (IEC/EN 60529)  
> 1.9 Mio. h  
Reliability, calculated MTBF (at 25°C acc. to IEC 61709)  
* Output voltage can be adjusted as indicated. However, output power has to be maintained at nominal value.This means the output  
nominal current has to be reduced in accordance with the increase of output voltage.  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
http://www.tracopower.com  
Page 2 of 5