Industrial Power Supplies
TBL Series
15 to 150 Watt
Input Specifications
Input voltage
– nominal
– AC range
100 – 240 VAC
85 – 264 VAC (output power derating 5 %/V
for opertion below 90 VAC)
Input frequency
Harmonic limits
47 – 63 Hz
EN 61000-3-2, Class A
Output Specifications
Output voltage adjustable range
5 VDC model: 5.0 – 5.2 VDC
12 VDC models: 12 – 16 VDC
24 VDC models: 24 – 28 VDC
Output regulation
1 %
Ripple and noise (20MHz bandwidth)
Electronic short circuit protection
< 100 mV pk-pk
current limitation at 100 – 150 % typ.
(automatic recovery)
Hold-up time
115 VAC
min. 10 ms
230 VAC
min. 20 ms
General Specifications
Temperature ranges
– Operating
– 25 °C to +70 °C max.
2.5 %/K above 60 °C
5 – 95 % rel. H
Power derating
Humidity (non condensing)
Temperature coefficient
Safety standards
0.02 %/K
UL 508, UL 1310, class II
IEC/EN 60950-1, UL 60950-1, EN 50178,
EN 60204, EN 61558-2-8
CSA C22.2 No. 60950-1 2003
Safety approvals
(TBL 150 models pending)
– CB report
IEC/EN 60950-1
www.tracopower.com/products/tbl_cb60950-1.pdf
UL 508 listed
– UL approval
www.tracopower.com/products/tbl_ul508.pdf
UL 1310 listed
www.tracopower.com/products/tbl_ul1310.pdf
UL 60950-1, CSA 60950-1-03
www.tracopower.com/products/tbl_csa60950-1.pdf
www.tracopower.com/products/tbl_gs.pdf
– CSA certification
– GS certification
Electromagnetic compatibility (EMC), emissions
– Conducted RI suppression on input
– Radiated RI suppression
EN 61000-6-3
EN 55022 class B
EN 55022 class B
Electromagnetic compatibility (EMC), immunity
EN 61000-6-2
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity line – ground
– Surge immunity line – line
– Surge immunity output
– Immunity to conducted RF disturbances
– Mains voltage dips and interruptions
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
4 kV / 8 kV
3 V/m
1 kV / 0.5 kV
2 kV
1 kV
0.5 kV
3 V
EN 61000-4-11 30 % /10 mS, 60 % /100 mS
http://www.tracopower.com