Industrial Power Supplies  
TBL Series  
15 to 150 Watt  
Input Specifications  
Input voltage  
– nominal  
– AC range  
100 – 240 VAC  
85 – 264 VAC (output power derating 5 %/V  
for opertion below 90 VAC)  
Input frequency  
Harmonic limits  
47 – 63 Hz  
EN 61000-3-2, Class A  
Output Specifications  
Output voltage adjustable range  
5 VDC model: 5.0 – 5.2 VDC  
12 VDC models: 12 – 16 VDC  
24 VDC models: 24 – 28 VDC  
Output regulation  
1 %  
Ripple and noise (20MHz bandwidth)  
Electronic short circuit protection  
< 100 mV pk-pk  
current limitation at 100 – 150 % typ.  
(automatic recovery)  
Hold-up time  
115 VAC  
min. 10 ms  
230 VAC  
min. 20 ms  
General Specifications  
Temperature ranges  
– Operating  
– 25 °C to +70 °C max.  
2.5 %/K above 60 °C  
5 – 95 % rel. H  
Power derating  
Humidity (non condensing)  
Temperature coefficient  
Safety standards  
0.02 %/K  
UL 508, UL 1310, class II  
IEC/EN 60950-1, UL 60950-1, EN 50178,  
EN 60204, EN 61558-2-8  
CSA C22.2 No. 60950-1 2003  
Safety approvals  
(TBL 150 models pending)  
– CB report  
IEC/EN 60950-1  
www.tracopower.com/products/tbl_cb60950-1.pdf  
UL 508 listed  
– UL approval  
www.tracopower.com/products/tbl_ul508.pdf  
UL 1310 listed  
www.tracopower.com/products/tbl_ul1310.pdf  
UL 60950-1, CSA 60950-1-03  
www.tracopower.com/products/tbl_csa60950-1.pdf  
www.tracopower.com/products/tbl_gs.pdf  
CSA certification  
– GS certification  
Electromagnetic compatibility (EMC), emissions  
– Conducted RI suppression on input  
– Radiated RI suppression  
EN 61000-6-3  
EN 55022 class B  
EN 55022 class B  
Electromagnetic compatibility (EMC), immunity  
EN 61000-6-2  
– Electrostatic discharge (ESD)  
– Radiated RF field immunity  
– Electrical fast transient / burst immunity  
– Surge immunity line – ground  
– Surge immunity line – line  
– Surge immunity output  
– Immunity to conducted RF disturbances  
– Mains voltage dips and interruptions  
EN 61000-4-2  
EN 61000-4-3  
EN 61000-4-4  
EN 61000-4-5  
EN 61000-4-5  
EN 61000-4-5  
EN 61000-4-6  
4 kV / 8 kV  
3 V/m  
1 kV / 0.5 kV  
2 kV  
1 kV  
0.5 kV  
3 V  
EN 61000-4-11 30 % /10 mS, 60 % /100 mS  