内容描述: [Thermal Magnetic Circuit Breaker,]
分类和应用: 电路保护
文件页数/大小: 2 页 / 97 K
品牌: SCHNEIDER [ SCHNEIDER ELECTRIC ]
 浏览型号24205的Datasheet PDF文件第2页  
Product datasheet
Characteristics
24205
C60 - circuit breaker - C60N - 2P - 32A - C curve
Range of product
Range
Product name
Product or component type
Device short name
Device application
Poles description
Number of protected poles
[In] rated current
Network type
Trip unit technology
Curve code
Breaking capacity
C60
Multi 9
C60
Miniature circuit-breaker
C60N
Distribution
2P
2
32 A at 30 °C
DC
AC
Thermal-magnetic
C
10 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898
20 kA Icu at 125 V DC conforming to EN/IEC 60947-2
20 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 125 V DC conforming to EN/IEC 60947-2
40 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2
Yes conforming to IEC 60947-2
Suitability for isolation
Complementary
Network frequency
[Ue] rated operational voltage
50/60 Hz
440 V AC 50/60 Hz
230...240 V AC 50/60 Hz
400...415 V AC 50/60 Hz
<= 250 V DC
230/400 V AC 50/60 Hz
5...10 x In
7.5 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz
2.25 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
3.75 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz
6000 A conforming to EN 60898 - 230/400 V AC 50/60 Hz
3 conforming to EN/IEC 60947-2
Magnetic tripping limit
[Ics] rated service breaking capacity
Limitation class
23 Jul, 2019