232B - 232E
Only One Name Means ProTek’Tion™
TyPICAL DEꢀICE ChARACTERISTICS
MAXIMUM RATINGS @ 25°C Unless Otꢁerwise Specified
PARAMETER
SyMBOL
ꢀALUE
±25
UNITS
Volts
mA
Peak Operaꢀng Line Voltage
Operaꢀng Line Current
Transient Voltage
VOP
IO
200
-
10
kV/Wire
kA/Wire
°C
Transient Current - 8/20µs waveform
Operaꢀng Temperature
Storage Temperature
-
10
TA
TSTG
-
-55 to 100
-55 to 100
< 1
°C
Response Time
ns
ELECTRICAL ChARACTERISTICS PER LINE @ 25°C Unless Otꢁerwise Specified
PART
NUMBER
MAXIMUM
CLAMPING
ꢀOLTAGE
(8/20µs)
MAXIMUM
LINE
ThROUGhPUT
RESISTANCE
MAXIMUM
LEAKAGE
CURRENT
MAXIMUM
CAPACITANCE
ꢂ 500A
ꢀC
ꢀOLTS
ꢂ 25ꢀOP
ꢂ 0ꢀ, 1Mhz
R
ID
µA
C
pF
OhMS
232B/E
40
12
5
2000
INSTALLATION INSTRUCTIONS
There are five (5) terminals on both the line and equipment side of the 232E - four data line terminals and two ground terminals. Both ground terminals, as shown on
the label, are connected internally. A single ground connecꢀon is suꢁcient. However, it is recommended that both ground connecꢀons be used for a lower imped-
ance path to earth. This connecꢀon can be made through the green AC power ground wire or a known earth ground. The ground wire should be #14 stranded wire.
Incoming data lines are cut or disconnected from the equipment to insert the 232E product. The line side of the terminals are to be connected to data lines from the
outside world or lines that carry the transient threats into the equipment to be protected. The equipment side of the terminals are to be connected to the equipment
to be protected . The locaꢀon of the product should be such that these wires are as short as possible. A #18 or 20 gauge wire can be used for these connecꢀons.
Protectors should be installed at both ends of the data lines, at the point of entry to buildings. Use the shortest possible connecꢀon to a low impedance earth ground.
Proper grounding and bonding are essenꢀal for computer installaꢀon applicaꢀons.
The 232B circuit board requires an edge connector interface for installaꢀon. The circuit board should be located at the building interface for incoming lines from the
outside world.
Both the 232B and 232E can be mounted on a data line circuit panel, which must be hard wired to the incoming data lines. Unprotected input lines and ground wires
are to be separated from protected output lines to prevent electromagneꢀc coupling of noise from high transient currents on the input lines.
ProTek’s data line protector is designed with a short circuit failure mode to give maximum protecꢀon. A fuse, fusible link, or circuit breaker is recommended for each
data/signal line on the input (line) side of the protector for those applicaꢀons that require an open circuit failure mode.
Cauꢃon: A low DC resistance ground may not be indicaꢀve of a good lightning ground. Lightning contains a broad spectrum of frequencies - up to 1 MHz. A low
impedance path to ground at the transient frequencies is necessary. A ground strap is recommended or a #6 AWG stranded wire. For wire lengths over 1.5 meters,
there may be some excessive line to earth potenꢀal under severe thunderstorm condiꢀons. For these applicaꢀons, an addiꢀonal protector may be necessary at the
equipment interface.
www.protekdevices.com
05060.R5 9/12
Page 2