ModSTACKTM
Datasheet: B6I 690/1100-250G M, S
Preliminary Data
After overcurrent
message by
PowerSTACK
Interface
Overcurrent Shut
Down Reaction Time
10
µs
Mechanical Data
Airvelocity
vAir
dV/dtAir
∆pAir
t.b.d
800
m/s
m³/h
Pa
ϑAir=20°C
Airflow heatsink
Air Pressure Drop
heatsink
Pair=1013 hPa
Dry- and dustfree,
measured outside of
heatsink.
130
According DIN 41882
According
Watervelocity
Waterflow heatsink
vWater
dV/dt
Water
m/s
m³/h
Coolingwater
Specification from
eupec
-
Water Pressure Drop
heatsink
-
Pa
∆pWater
Width x Depth x Hight
Approximation
Dimensions
Mass
Storage Temperature
Range
Operating
Temperature range
(PCB and Capacitor)
Cooling Air Inlet
Temperature
702
-40
540
45
304
+65
+55
mm
kg
°C
ϑstor
ϑop
Minimal 0 °C for
optional optical
interface
-25 (0)
°C
°C
-25
2
+40
ϑair_inlet
(Heatsink)
Cooling Airvelocity
(PCB and Capacitor)
Air Pressure
vAir_PCB
m/s
Standard atmosphere
No Condensation
pAir
Rel. F
900
0
1100
95
hPa
%
Humidity
Installation Height
Vibration
0
1000
10
m
m/s²
EN60068-2-6, Fc
10..59Hz 0,075mm
EN60068-2-6, Fc
Permanence Vibration
Shock
20
m/s²
m/s²
10-150Hz, 20 Cycles
EN60068-2-27, Ea
Halfsine 11ms, 3 pulses
100
Protection Degree
Pollution Degree
IP00
2
Overvoltage Category
III
B6I690-1100-250G.doc
4 of 9
2005-03-18