E
3
Technical Specification  
EN/LZT 146 377R3FJun 2008  
PKB4000C PI  
© Ericsson Power Modules AB  
DC/DC Converters, Input 36-75 V, Output 60 A/144 W  
Safety Specification  
Isolated DC/DC converters  
It is recommended that a slow blow fuse with a rating  
twice the maximum input current per selected product be  
used at the input of each DC/DC converter. If an input filter  
is used in the circuit the fuse should be placed in front of  
the input filter.  
General information  
Ericsson Power Modules DC/DC converters and DC/DC  
regulators are designed in accordance with safety  
standards IEC/EN/UL60950, Safety of Information  
Technology Equipment.  
In the rare event of a component problem in the input filter  
or in the DC/DC converter that imposes a short circuit on  
the input source, this fuse will provide the following  
functions:  
IEC/EN/UL60950 contains requirements to prevent injury  
or damage due to the following hazards:  
Electrical shock  
Energy hazards  
Fire  
Mechanical and heat hazards  
Radiation hazards  
Chemical hazards  
Isolate the faulty DC/DC converter from the input  
power source so as not to affect the operation of  
other parts of the system.  
Protect the distribution wiring from excessive  
current and power loss thus preventing  
hazardous overheating.  
On-board DC-DC converters and DC/DC regulators are  
defined as component power supplies. As components  
they cannot fully comply with the provisions of any Safety  
requirements without “Conditions of Acceptability”.  
Clearance between conductors and between conductive  
parts of the component power supply and conductors on  
the board in the final product must meet the applicable  
Safety requirements. Certain conditions of acceptability  
apply for component power supplies with limited stand-off  
(see Mechanical Information for further information). It is  
the responsibility of the installer to ensure that the final  
product housing these components complies with the  
requirements of all applicable Safety standards and  
Directives for the final product.  
The galvanic isolation is verified in an electric strength test.  
The test voltage (Viso) between input and output is  
1500 Vdc or 2250 Vdc for 60 seconds (refer to product  
specification).  
Leakage current is less than 1 µA at nominal input voltage.  
24 V DC systems  
The input voltage to the DC/DC converter is SELV (Safety  
Extra Low Voltage) and the output remains SELV under  
normal and abnormal operating conditions.  
48 and 60 V DC systems  
If the input voltage to the DC/DC converter is 75 Vdc or  
less, then the output remains SELV (Safety Extra Low  
Voltage) under normal and abnormal operating conditions.  
Component power supplies for general use should comply  
with the requirements in IEC60950, EN60950 and  
UL60950 “Safety of information technology equipment”.  
There are other more product related standards, e.g.  
IEEE802.3af “Ethernet LAN/MAN Data terminal equipment  
power”, and ETS300132-2 “Power supply interface at the  
input to telecommunications equipment; part 2: DC”, but  
all of these standards are based on IEC/EN/UL60950 with  
regards to safety.  
Single fault testing in the input power supply circuit should  
be performed with the DC/DC converter connected to  
demonstrate that the input voltage does not exceed  
75 Vdc.  
If the input power source circuit is a DC power system, the  
source may be treated as a TNV2 circuit and testing has  
demonstrated compliance with SELV limits and isolation  
requirements equivalent to Basic Insulation in accordance  
with IEC/EN/UL60950.  
Ericsson Power Modules DC/DC converters and DC/DC  
regulators are UL60950 recognized and certified in  
accordance with EN60950.  
Non-isolated DC/DC regulators  
The flammability rating for all construction parts of the  
products meets requirements for V-0 class material  
according to IEC 60695-11-10.  
The input voltage to the DC/DC regulator is SELV (Safety  
Extra Low Voltage) and the output remains SELV under  
normal and abnormal operating conditions.  
The products should be installed in the end-use  
equipment, in accordance with the requirements of the  
ultimate application. Normally the output of the DC/DC  
converter is considered as SELV (Safety Extra Low  
Voltage) and the input source must be isolated by  
minimum Double or Reinforced Insulation from the primary  
circuit (AC mains) in accordance with IEC/EN/UL60950.