Technical Specification  
BMR454 series Fully regulated Intermediate Bus Converters  
EN/LZT 146 404 R7A March 2013  
© Ericsson AB  
Input 36-75 V, Output up to 40 A / 240 W  
circuit on the input source, this fuse will provide the  
following functions:  
Safety Specification  
General information  
Isolate the fault from the input power source so as not  
to affect the operation of other parts of the system  
Protect the distribution wiring from excessive current  
and power loss thus preventing hazardous overheating  
Ericsson Power Modules DC/DC converters and DC/DC  
regulators are designed in accordance with the safety  
standards IEC 60950-1, EN 60950-1 and UL 60950-1  
Safety of Information Technology Equipment.  
The DC/DC converter output is considered as safety extra  
low voltage (SELV) if one of the following conditions is met:  
IEC/EN/UL 60950-1 contains requirements to prevent injury  
or damage due to the following hazards:  
The input source has double or reinforced insulation  
from the AC mains according to IEC/EN/UL 60950-1  
The input source has basic or supplementary insulation  
from the AC mains and the input of the DC/DC  
converter is maximum 60 Vdc and connected to  
protective earth according to IEC/EN/UL 60950-1  
The input source has basic or supplementary insulation  
from the AC mains and the DC/DC converter output is  
connected to protective earth according to  
Electrical shock  
Energy hazards  
Fire  
Mechanical and heat hazards  
Radiation hazards  
Chemical hazards  
On-board DC/DC converters and DC/DC regulators are  
defined as component power supplies. As components  
they cannot fully comply with the provisions of any safety  
requirements without “conditions of acceptability”.  
Clearance between conductors and between conductive  
parts of the component power supply and conductors on  
the board in the final product must meet the applicable  
safety requirements. Certain conditions of acceptability  
apply for component power supplies with limited stand-off  
(see Mechanical Information for further information). It is  
the responsibility of the installer to ensure that the final  
product housing these components complies with the  
requirements of all applicable safety standards and  
regulations for the final product.  
IEC/EN/UL 60950-1  
Non - isolated DC/DC regulators  
The DC/DC regulator output is SELV if the input source  
meets the requirements for SELV circuits according to  
IEC/EN/UL 60950-1.  
Component power supplies for general use should comply  
with the requirements in IEC/EN/UL 60950-1 Safety of  
Information Technology Equipment. Product related  
standards, e.g. IEEE 802.3af Power over Ethernet, and  
ETS-300132-2 Power interface at the input to telecom  
equipment, operated by direct current (dc) are based on  
IEC/EN/UL 60950-1 with regards to safety.  
Ericsson Power Modules DC/DC converters and DC/DC  
regulators are UL 60950-1 recognized and certified in  
accordance with EN 60950-1. The flammability rating for all  
construction parts of the products meet requirements for  
V-0 class material according to IEC 60695-11-10, Fire  
hazard testing, test flames – 50 W horizontal and vertical  
flame test methods.  
Isolated DC/DC converters  
Galvanic isolation between input and output is verified in an  
electric strength test and the isolation voltage (Viso) meets  
the voltage strength requirement for basic insulation  
according to IEC/EN/UL 60950-1.  
It is recommended to use a slow blow fuse at the input of  
each DC/DC converter. If an input filter is used in the circuit  
the fuse should be placed in front of the input filter. In the  
rare event of a component problem that imposes a short