Film capacitors – Capacitors for Power Factor Correction  
WindCap capacitors  
B25668A6836A375  
MKK690-D-12.5-11  
Terminals  
Degree of protection  
Max. torque  
Isolated terminals, IP20  
1.2 Nm  
Terminal cross section  
Maximum terminal current  
Creepage distance  
Clearance  
16 mm2 (5 AWG)  
50 A  
12.7 mm  
9.6 mm  
Safety  
Mechanical safety  
Max. short circuit current  
Discharge resistor time  
Overpressure disconnector  
AFC: 10 kA  
1 min (75 V)  
Reference Standards  
IEC 60831-1/2, UL 810 (5th edition)  
Certification: cUL file E238746  
Cautions and warnings  
ƒ
In case of dents of more than 1 mm depth or any other mechanical damage, capacitors must not  
be used at all.  
ƒ
ƒ
This applies also in cases of oil leakages.  
To ensure the full functionality of the overpressure disconnector, elastic elements must not be  
hindered and a minimum space of 12 mm has to be kept above each capacitor.  
ƒ
ƒ
ƒ
Do not handle the capacitor before it is discharged.  
Resonance cases must be avoided by appropriate application design in any case.  
Handle capacitors carefully, because they may still be charged even after disconnection due to  
faulty discharging devices.  
ƒ
ƒ
Protect the capacitor properly against over current and short circuit.  
Failure to follow cautions may result, worst case, in premature failures, bursting and fire.  
Discharging  
Capacitors must be discharged to a maximum of 10% of rated voltage before they are switched on  
again. This prevents an electric impulse discharge in the application, influences the capacitor’s  
service life and protects against electric shock. The capacitor must be discharged to 75 V or less  
within 3 minutes. There must be not any switch, fuse or any other disconnecting device in the circuit  
between the power capacitor and the discharging device. Discharge and short circuit capacitor before  
handling!  
FK PFC R&D  
July 2007  
Page 4 of 8