Power Capacitors
Power Factor Correction
Construction
Dielectric: Polypropylene film
Gas-impregnated / dry type
Concentric winding
Wave cut
Extruded round aluminum can with stud
Provided with ceramic discharge module
Triple safety system
Features
Three phase, delta connected
Self-healing technology
Naturally air cooled (or forced air cooling)
Indoor mounting
Typical applications
For Power Factor Correction
Terminals
SIGUT terminals
Mounting parts
Threaded stud at bottom of can
(
max. torque = 10 Nm for M12)
B25667B4347A375
MKK480-D-25-01
Dimensional drawing
Technical data and specifications
Characteristics
Rated capacitance C
R
Tolerance
Connection
Rated voltage V
R
Rated frequency f
R
Output
Rated current I
R
tan (dielectric)
*) valid for -40/B
3 x 115 µF
-5 / +10%
D (Delta)
480 VAC
50 Hz
25 kvar
30 A
0.2 W / kvar
60 Hz
30kvar*)
36A
FK PFC RD / CA
Page 1 of 3
Edition 4.
01.12.06