ADN-C Series
2 of 3
General Specifications
EMC Emissions:
EN61000-6-2:2001, EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex.
A, EN61000-3-2
EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3,
EN61000-4-4 Level 4 input and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, IEC 61000-4-34
voltage dip immunity standard
EMC Immunity:
Warranty:
5 Years
Protected against continuous short-circuit, continuous overload, continous open circuit. Protection Class 1
(IEC536), degree of protection IP20 (IEC60529) Safe low voltage: SELV (acc. IEC60950-1)
General protection safety:
Visual: 3 status LEDs (Input, Output, Alarm)
Relay: N.O. contact rated 200 mA/50 Vdc
Status Indicators:
LED Diagnostics
LED
OK
Loss of Ac
Low Ac
No Dc
High Load
Overload
Hot
Too Hot
• Input
Green
Green
---
---
---
---
Yellow
Green
---
Green
---
Green
Yellow
Yellow
Green
Yellow
Red
Green
Green
Yellow
Green
---
• Output
• Alarm
Red
Yellow
Environmental Specifications
Storage/shipment:
-25 °C to + 85 °C
ADN5-24-1PM-C & ADN10-24-1PM-C:
ADN20-24-1PM-C:
Full Load -10 °C to + 60 °C derate to 50% load at +70 °C
Full Load -25 °C to + 60 °C derate to 50% load at +70 °C
Operation (convection):
Up to 50% load permissable with horizontal or on top mounting orientation
Other Features
External fusing:
Not required. Unit provides internal fuse (not accessible)
Standard: Vertical, Optional: Horizontal or on Top
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system
Mounting orientation:
Ventilation:
Normal convection, No fan required
ADN5-24-1PM-C & ADN10-24-1PMC:
ADN20-24-1PMC:
15 mm in front, 25 mm above and below, 10 mm left and right
15 mm in front, 40 mm above and below, 10 mm left and right
Cooling Spacing
Input: Screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors
Connections:
Output: Two terminals per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors