SNAP Analog Input Modules
0 to 10 Amp RMS AC/DC Input Module
Part Number
Description
Description
SNAP-AIARMS Two-channel 0 to 10 amp RMS AC/DC input
The SNAP-AIARMS module provides an input range of 0 to 10
amps RMS AC/DC. An ideal input is the 5-amp secondary of a
standard current transformer used to monitor AC line current.
Specifications
The SNAP-AIARMS module may be used to monitor AC
current to greater than a 100-amp range, using a current
transformer of suitable ratio.
Input Range
0 to 10 amp RMS AC/DC
To 11 amps
Input Over-Range
Input Resistance
Maximum Input
Accuracy (AC)
Resolution
0.005 ohms
If you need a module with channel-to-channel isolation, see
form #1182, the SNAP Isolated Analog Input Modules Data
Sheet.
11 amps AC/DC
±8 mA and ±0.2% reading
400 microamps
Wiring diagrams are on the following page.
DC Reversal
±16 mA (0.16%)
Input Response Time
(Step Change)
63.2% (158 V) in 50 mS
99% (248 V) in 75 mS
Data Freshness (Max)
32.3 ms
DC Common Mode Rejec-
tion
>-120 dB
AC Common Mode Rejec-
tion
>-120 dB at 60 Hz
250 V
Maximum Operating Com-
mon Mode Voltage
Isolation
1500 V
Power Requirements
Operating Temperature
Storage Temperature
Wire size
5 VDC (±0.15 V) at 170 mA
0 °C to 70 °C
-40 °C to 85 °C
22 to 14 AWG
Torque, hold-down screws 4 in-lb (0.45 N-m)
Torque, connector screws 5.26 in-lb (0.6 N-m)
Agency Approvals
Warranty
UL, FM, CE, RoHS, DFARS
Lifetime
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
PAGE
4
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2001–2014 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.