celduc
S/GRA/SWTA4610/B/23/07/2002
r
e
l
a
i
s
Page 4/6 GB
INTERNAL POWER SUPPLY
CHARACTERISTIC
LABEL
VALUE
INFO.
Terminals
3L2 & 5L3
200->480VAC
1mA typical
40-65Hz
Mains voltage range
Consumption
Ue
Is
Mains frequency range
Turn-on time
F
tm
100ms
GENERAL INFORMATION
Connections
Power
Posidriv 2 or 0.8 x 5.5mm
1.8->3N.m
Input terminal block
Screwdriver advised
Min and max tightening torque
0.8 x 2mm
2
Number and cross section of the
wires
2 x 1.5->6mm
2
1 x 2.5mm
2
(10mm without ferrule)
Screwdriver for settings
0.8 x 2mm
Housing
Mounting
Noise level
Weight
UL94V0
Omega DIN rail (DIN50022) or screwed
Low audible vibrations
500g
STANDARDS
Standards
EN60947-4-2 & EN60947-4-3
IP2L0
Protection level
Accordin to V.D.E. 160 part 100 :
Back hand and finger safety
Protection against direct touch
CE marking
Yes
UL, cULUS and VDE approvals
Pending
STANDARD
TYPE OF TEST
LEVEL
EFFECT
8kV (air)
EN61000-4-2
EN61000-4-3
EN61000-4-4
E.S.D. (Electrostatic discharges)
Radiated electromagnetic fields
Fast transients bursts
No effect
No effect
No effect
4kV (touch)
10V/m
2kV direct coupling on the power side
2kV coupling by clamp on the input side
1kV direct coupling differential mode (input and output)
2kV direct coupling common mode (input and output)
EN61000-4-5
EN61000-4-11
Electric chocks
Voltage drop
No effect
-
The conducted or radiated disturbances generated by
solid state relays depend on the wiring and load
configuration.
The test method recommended by the European standards
Radiated and conducted
disturbances
NFEN55011 and concerning electromagnetic compatibility leading to
results far from reality, we decided to advise our customer
in order to adapt their filtering scheme to their application.
Please refer to the SVTA – SWTA installation