S/MOT/SW961230/A/16/03/2000
page 3 / 5 F/GB
Tension nominale/ Standard mains voltage
Ue
Un
Up
Ie
Pn
Ud
400 VAC
24-520VAC
1600V
8,5ARMS
4KW
Plage de tension de fonctionnement / Mains voltage range
tension crête non répétitive/ Non-repetitive maximum peak voltage
Courant AC-53 maxi/ Max. nom. current (AC53a=AC3) @40°C
Puissance moteur/ 3 pole power motor ( 3x400VAC)
Chute directe / Max Direct voltage drop (@Ie)
1,4VRMS
Courant crête non répétitif/ Non repetitive overload current
(@ 1 cycle of 10ms)
I2t value/ Melting limit (choice of fuse) @10ms
Courant minimal de charge / Minimum load current
facteur de puissance/ Power factor (@ Ith)
ITSM
550A
I2t
Imin
Pf
1500 A2s
100 mA
0 up to 1
Temps d'ouverture et de temporisation/ Turn on time-reversing time(@50Hz)
Temps d'ouverture/ Turn off time (@50Hz)
Courant de fuite /Maximum leakage current (@Ue/50Hz)
dv/dt / Max off state voltage rise
Fréquence de réseau / Operating frequency range
ton/trv
toff
Ilk
dv/dt
f
20ms / 100ms
10ms
5 mARMS
500V/µs
25 up to 440Hz
4KV direct at output, 4KV with a clamp at input
Max conducted immunity level
Test accord. to I.E.C.1000-4-4 (bursts)
Max conducted immunity level
Test acc. to I.E.C.1000-4-5 (el. shocks)
Max radiated immunity level
no turn on or damage
2KV in common mode, 1KV in differential mode (Input & output)
no turn on or damage
10V/m
no turn on or damage
Test accord. to I.E.C.1000-4-3
Max electrostatic disch. immunity level
Test accord. to I.E.C.1000-4-2
Max conducted emission level (0,8<Pf<1)
Test according to EN55011
8KV in the air / 4KV touching
no turn on or damage
The conducted noise made by SSR depends on the wiring configuration and the load type. Test
methods recommended by European E.M.C. standards giving results far from reality, we have
chosen to advise the right filter suited for the customer's use: Refer to EMC chapter
Max radiated emission level
Test accord. to EN55011 @Ie
<30dBµV from 30 up to 230MHz ; <37dBµV from 230 up to 1000MHz
Base/junction thermal resistance
Rthjc
Rthja
0,5K/W (1 leg)
Ambient/junction thermal resistance
(relay mounted vertically)
Weight
5K/W
130g
Characteristics given at 25°C unless otherwise specified
REVERSERS + HEATSINK SELECTION IN COMPLIANCE WITH EN60947-4-2
SSR SELECTION
motors soft-staters
for a permanent current
Relays with heatsink
Ferraz fuse type
Overload relay type
14x51 size / max. rating
Klöckner-Moeller
Motor power In motor
two legs
ambient =40°C
(@
400V)
2A
SW960330 (See data-sheet)
SW960330 (See data-sheet)
SW960330 (See data-sheet)
SW961230
am 8A/500V
am 8A/500V
am 12A/500V
am 12A/500V
am 12A/500V
am 12A/500V
Z00-2.4
Z00-6
0,75 kW
1,1 kW
1,5 kW
2,2 kW
3 kW
2,6A
3,5A
5A
6,6A
8,5A
Z00-6
Z00-6
SW961230
Z00-10
Z00-10
4 kW
SW961230
For motor > 4kW consult us : we have some solutions