S/CLP/SIM865170/B/21/04/2004
®
celpac
page 4 / 4GB
wires
torques
screwdriver
Connections .
L
L
(mm2)
Ø
For the output terminals, the wire cross sections must
screwdriver
be adapted to the load current and to the overcurrent protection
device characteristics. The relay rated voltage must be adapted
to the mains rated voltage.
control
1 x(0,75-->2,5)
L = 6mm
0,4N.m
(0,6N.m max)
3,5x0,5mm
Ø
celpac use screw clamp connections.
Power
1x(1,5-->16) 1 x(1,5-->10)
L = 10mm
1,2N.m
(1,8N.m max)
Pozidriv2/
0,8x5,5 (1x6)
Mounting
Ø
Warning : only in vertical position. The user should protect heat sensitive materials as
well as persons against any contacts with the heatsink. For non vertical mounting , the load
current must be 50% lower than the rated one . For a good cooling, the SSR needs an air
convection. Less convection air produces an abnormal heating. Keep a distance between
the upper SSR and the lower SSR. In case of no space between two SSR ( zero space
between two SSRs) , please reduce the load current. For further details refer to below :
Ø Derating current with no space between SSRs
AC-51 nominal currents are given with a space of 22,5mm between each SSR, for a
permanent current during a minimum time of 8 hours in air calm according to IEC60947-4-3.
In case of non permanent currents or in case of SSRs are mounted with no space, you must
check the heatsink temperature never exceed 90°C. When the SSRs are mounted side to
side ( no space between each relay) a derating current of 25% must be take into account.
A forced cooling ( fan inside the cabinet) improves significantly the thermal performances.
vert ical
posit ion
8 0 mm
Typical application : LOADS
SIL product is designed mainly for AC-51 résistive load. AC-53 motor current are
also given . For other loads, check the inrush current at turn ON and possible overvoltages
at turn OFF or consult us :
* AC-55b : Incandescent lamps : Inrush current is generally 10 times In during few 10ms.
So limit the nominal current at about 15A.
* AC-55a : Electric discharge lamp : These loads often have overcurrent at turn ON and
overvoltage at turn OFF, so we advise to use 400VAC SSR on 230VAC mains.
* AC-56a : Transformers loads : Very high inrush current up to 100 times In . We advise to
use random SSR.
1 ~
* AC-56b : Capacitors loads : Very high current at turn ON and overvolatge at turn OFF,
please consult us with 1600V peak SSR with high inrush current.
Fuse
Fusible
Protection :
2
2
To protect the SSR against a short-circuit of the load , use a fuse with a I t value = 1/2 I t
value specified page 2. A test has been made with FERRAZ fuse ( see page 2).
L1
T1
It is possible to protect SSR by MCB ( miniature circuit breaker). In this case, see application
2
2
note ( SSR protection) and use a SSR with high I t value (5000A s minimum).
EMC :
Ø
Immunity :
We give in our data-sheets, the immunity level of our SSRs according to the main
standards for this type of products : EN61000-4-4 &5. You can see the high immunity level
in comparison with the products on the market.
+
-
A1
A2
Ø
Emission:
cont rol
SSRs are complex devices which must be interconnected with other equipment
Load
Charge
(loads, cables,etc.) to form a system. Because the other equipment or the interconnections
may not be under the control of celduc, it shall be the responsibility of the system integrator
to ensure that systems containing SSRs comply with the requirements of any rules and
regulations applicable at the system level. The very low zero cross voltage (<20V) improves
the conducted emission level in comparison with most of SSR on the market with zero cross
voltage higher than 50V. Consult celduc laboratory which can make some tests in your
application.