 浏览型号2033-C0860H-71K的Datasheet PDF文件第1页浏览型号2033-C0860H-71K的Datasheet PDF文件第2页浏览型号2033-C0860H-71K的Datasheet PDF文件第4页浏览型号2033-C0860H-71K的Datasheet PDF文件第5页浏览型号2033-C0860H-71K的Datasheet PDF文件第6页浏览型号2033-C0860H-71K的Datasheet PDF文件第7页浏览型号2033-C0860H-71K的Datasheet PDF文件第8页浏览型号2033-C0860H-71K的Datasheet PDF文件第9页  
Safety Isolation System  
ElectroGuard  
Overview  
Principle of Operation  
After using the normal stopping  
method of the machine or process,  
the machine operator turns a  
Remote Lockout Station handle  
from the “On” to “Offposition.  
The station signals the isolation  
contactors (1IC and 2IC) to drop  
out and isolate the supply voltage  
from the loads (see Control  
Circuit).  
Power Circuit  
2IC  
1IC  
Incoming  
3 Phase  
Power  
To M o to r  
To Lo ad s  
Controllers  
H1 H2  
GC  
Trans.  
X2  
X1  
Control Power  
Voltage  
Decay  
Relays  
(VDR)  
When system residual voltage  
decays to pre-determined levels,  
the grounding contactor (GC) is  
energized, connecting the load to  
ground (see Power Circuit). The  
grounding contactor (GC) is  
electrically and mechanically  
interlocked with the isolation  
contactors (1IC and 2IC).  
Grd  
Disconnecting  
Means/Branch  
Circuit Protection ➊  
The “System Isolated” Light will  
now illuminate on the Remote  
Lockout Station to indicate the  
system is isolated. The machine  
operator then Locks-Out and  
Tags-Out the station in the “Off”  
position.  
Control Circuit  
Remote Lockout Station  
Off  
On  
GC  
1IC  
Mechanically  
Interlocked  
GC  
2IC  
VDR  
GC  
1IC  
1IC  
2IC  
1IC, 2IC, &  
GC are  
mechanically  
and electrically  
interlocked  
GC  
System Isolated (*)  
2IC  
(*) = “On” when the Remote  
Lockout Station switch is “Off”  
Available factory installed within the ElectroGuard as an option.  
Optional Features  
Four (4) or ten (10) port Expansion Modules to permit additional Remote  
Lockout Stations to be used (see page 12-16 for details).  
Pneumatic Isolation Module to isolate pneumatic energy (see page 12-15 for  
details).  
Status communication to a remote PLC (see page 12-17 for details).  
Fusible disconnect switch (Bulletin 2032) or thermal-magnetic circuit breaker  
(Bulletin 2033) to provide branch circuit protection.  
Optional Pneumatic Isolation Module  
12-3