 浏览型号2032-C0023PX-24B的Datasheet PDF文件第1页浏览型号2032-C0023PX-24B的Datasheet PDF文件第2页浏览型号2032-C0023PX-24B的Datasheet PDF文件第3页浏览型号2032-C0023PX-24B的Datasheet PDF文件第4页浏览型号2032-C0023PX-24B的Datasheet PDF文件第5页浏览型号2032-C0023PX-24B的Datasheet PDF文件第6页浏览型号2032-C0023PX-24B的Datasheet PDF文件第7页浏览型号2032-C0023PX-24B的Datasheet PDF文件第9页  
Safety Isolation System  
ElectroGuard  
Typical Wiring Diagram/Wire Length Considerations  
Total W ire Length for Expansion Modules  
Typical Wiring Diagram  
For North Am erica  
Max. Total  
For O utside North Am erica  
Safety Isolation System  
with Optional Fusible  
Disconnecting Means  
Max. Total  
W ire Length  
GC  
W ire Gauge  
W ire Length  
40,000 feet  
23,000 feet  
11,700 feet  
W ire Gauge  
14AWG  
18 Gauge Metric 12,200 meters  
14 Gauge Metric 7,000 meters  
16AWG  
18AWG  
Sample Calculation: An application for a 630A Safety Isolation  
System will require 8 Remote Lockout Stations (RLS):  
1IC 2IC  
L1  
T1  
To Motor  
Starters  
The wire length from RLS # 1 to the Control Module (in the  
ElectroGuard Power Panel) will be 50ft.  
L2  
L3  
T2  
T3  
To  
Loads  
The wire length from RLS # 2 to the Control Module will be 200ft.  
The wire length from RLS # 3 to the Control Module will be 100ft.  
The wire length from RLS # 4 to the Control Module will be 300ft.  
The wire length from RLS # 5 to the Control Module will be 500ft.  
The wire length from RLS # 6 to the Control Module will be 1000ft.  
The wire length from RLS # 7 to the Control Module will be 850ft.  
The wire length from RLS # 8 to the Control Module will be 750ft.  
Designates  
field  
connection  
points  
Remote  
Lockout  
Station(s)  
14AWG wire will be used to connect the RLS to the Control Module  
(see illustration below).  
Wire Length Considerations  
152m  
(500ft)  
304m  
(1000ft)  
259m  
(850ft)  
228m  
(750ft)  
ATTENTIO N: It is important not to  
exceed the maximum wire length values  
shown in this section. If the maximum values  
are exceeded, this may result in an unreliable  
signal to the Safety Isolation System.  
Consider using an Expansion Module if wire  
lengths greater than those shown for the  
Remote Lockout Stations are needed.  
RLS  
#5  
RLS  
#4  
RLS  
#8  
Expansion  
Module  
Each Remote Lockout Station is connected to the Control Module  
in the Power Panel of the Safety Isolation System. The total length  
of the wire used to connect the Remote Lockout Stations to the  
Control Module should not exceed the maximum values shown in  
the following tables.  
91m (300ft)  
30m (100ft)  
RLS  
#7  
RLS  
#3  
Control  
Module  
Calculate the total wire length as follows:  
RLS  
#6  
RLS  
#1  
61m (200ft)  
1. Determine the distance in feet or meters from each Remote  
Lockout Station to the Control Module (located inside the Safety  
Isolation System Power Panel).  
2. Sum the distances for all of the Remote Lockout Stations.  
3. Double this value.  
RLS  
#2  
Power Panel  
15m (50ft)  
4. Compare this doubled value with the maximum values for total  
wire length shown in the table below:  
Analysis: The Control Module furnished with the 630A Safety  
Isolation System is capable of supporting a maximum of six (6) RLS.  
Since this installation will require eight (8) RLS, an optional 4 port  
Expansion Module will also be used. The Expansion Module will be  
wired to the Control Module and will take the place of one of the  
original six RLS. We will, therefore, plan to wire five (5) of the RLS  
directly to the Control Module and three (3) of the RLS to the  
Expansion Module. Since the Expansion Module allows greater wire  
lengths than the Control Module, we will plan to wire the RLS to be  
installed furthest away from the Power Panel to the Expansion  
Module.  
Total W ire Length for Rem ote Lockout Stations  
For Nor th Am erica  
Max. Total  
For O utside of North Am erica  
Max. Total  
W ire Gauge  
18 Gauge Metric 1,400 meters  
14 Gauge Metric 800 meters  
W ire Gauge  
W ire Length  
W ire Length  
14AWG  
4,600 feet  
16AWG  
2,600 feet  
18AWG  
1,300 feet  
For RLS # 1: wire length = 50ft x 2 = 100ft  
For RLS # 2: wire length = 200ft x 2 = 400ft  
For RLS # 3: wire length = 100ft x 2 = 200ft  
For RLS # 4: wire length = 300ft x 2 = 600ft  
For RLS # 5: wire length = 500ft x 2 = 1000ft  
If the application requires a total wire length greater than those  
shown in the table, one or more Expansion Modules should be used.  
The maximum wire length for the Expansion Modules is shown in  
the following table:  
12-18